When it is needed
- Vibration readings have risen above the plant's alarm level
- A fan has had an impeller repair, a blade change or a build-up of material
- Bearings fail early and keep failing
- A new fan is being commissioned and the baseline needs recording
- Noise or vibration is felt in the structure, not just at the fan
What we do
- Measure vibration velocity and displacement at the bearings in three planes, with a spectrum to separate the frequencies
- Read the spectrum: once per revolution points to unbalance, twice to misalignment, blade pass to aerodynamic problems, bearing frequencies to the bearing
- Balance the rotor in situ by trial weights, in one or two planes as the rotor needs, to the grade the duty calls for
- Correct what balancing cannot: alignment, foundation bolting, clearances, resonance
- Record before and after readings against the severity chart
What you get
- A vibration report with spectra, the cause and the correction done
- A rotor balanced to grade G 6.3 or G 2.5 as per ISO 21940-11, with the record
- A baseline for the plant's condition monitoring to work from
Balancing cures unbalance. It does not cure a bent shaft or a soft foundation, and a fan balanced on top of either will shake again within the month. That is why the analysis comes first.