Home › Services & Support › Fan Energy Audit

Fan Energy Audit

A fan running against a throttled damper, oversized for the duty, or fitted with a worn or inefficient rotor can draw a third more power than the job needs. The audit measures the fan as it runs, works out the power the duty actually requires, and prices the gap.

When it is needed

What we do

  1. Measure the fan as it runs: flow, pressure, speed, power, damper position, gas condition
  2. Establish the duty the process needs now, which is often not the duty on the nameplate
  3. Calculate the fan efficiency and the system efficiency at the present point
  4. Model the options: damper opened and speed reduced by pulley change or VFD, rotor replaced with a higher efficiency design, impeller trimmed, fan replaced
  5. Price each option against the measured kWh and the plant's tariff, with the payback

What you get

The fan laws make the case: flow follows speed, pressure follows speed squared, power follows speed cubed. A fan running at 90% speed draws about 73% of the power. That is why a damper is the most expensive way to control flow.

Fans this applies to

Industries

Other services

Send us your duty point

Flow, pressure, gas condition and temperature are enough to start a selection.