Measurement of the fan at site: flow, static and total pressure, speed, power and gas condition, reduced to standard density and compared with the fan curve and the duty it was selected for.

When it is needed

What we do

  1. Traverse the duct with a pitot tube or anemometer at a straight run upstream and downstream of the fan, following the plane and point count the standard calls for
  2. Record static and total pressure at inlet and outlet, speed with a tachometer, motor current and voltage, gas temperature and, where it matters, moisture and dust loading
  3. Reduce every reading to standard density so the result can be laid on the manufacturer's curve
  4. Plot the measured operating point against the fan curve and the system curve, and state where the fan is running: at the duty, to the left of it in stall, or to the right of it at high power

What you get

Standards: IS 4894, BS 848 Part I, or the customer's own test standard. The report states which was used.