The process
Spinning mills run humidification plants that hold the department at the right humidity and waste collection systems that draw lint and fly from the machines into rotary filters. Large volumes of air at low pressure, with fibre that wraps a wheel.
The gas at the fan
Fibrous or stringy material that wraps a shrouded wheel. An open or straight radial impeller, spark resistant where the fibre is combustible, placed before or after the collector as the material allows.
Selection for this duty
| Impeller | PAG or die-cast aluminium impeller for low power, fixed or variable pitch |
| Form | Tube axial for low pressure; vane axial where the pressure or the downstream distribution calls for it; bifurcated where the motor must be out of hot or contaminated air |
| Also specified | Spark resistant construction and a flameproof motor |
| Density at the fan | At about 35°C the gas density is close to 1.15 kg/m³, 95% of standard air. Pressure developed and power drawn fall in the same ratio, so the selection is made at this density and the motor is checked at cold start. |
Supply, return and exhaust fans for heating, ventilation and air conditioning of plant and office space. Low pressure, so efficiency and noise govern. Client-stated blade types for the HVAC in general: Axial, backward inclined and forward curved.
Industries
Other fans in spinning mills
HVAC in other processes
Services on this fan
Information needed to select or quote
- Duty point. Volume flow and static pressure at the fan inlet, with the gas density and temperature or the conditions to derive it.
- Operating conditions. Site altitude, normal operating temperature and continuous or intermittent duty.
- Gas stream. Dust loading and particle size, corrosive species, moisture, upset temperature and any tendency of the material to deposit on the impeller.
- Mechanical. Rotation viewed from the drive end, discharge orientation and motor power.
