13, Galaxy Road, Ponniamman Nagar, Ayanambakkam, Chennai 600 095 +91 91766 67102  |  +91 91766 67103  |  marketing@adroitfantech.com
Home › Applications › HVAC › Dyeing and Finishing Houses

HVAC Fans for Dyeing and Finishing Houses

Supply, return and exhaust fans for heating, ventilation and air conditioning of plant and office space. In dyeing and finishing houses the gas at the fan is hot humid air, and that sets the blade form, the material and the drive.

The process

Dye houses are hot and humid, with steam and chemical vapour from the machines. Roof extractors and supply fans control the floor, fume extraction serves the chemical stores, and the boiler fan set serves the steam supply.

The gas at the fan

Air saturated with moisture from drying, with condensation on any cool surface. Drainage, a shaft seal and a material that tolerates wet running are part of the specification.

Selection for this duty

ImpellerSteel or cast aluminium impeller; PAG is not used above its temperature limit
FormTube axial for low pressure; vane axial where the pressure or the downstream distribution calls for it; bifurcated where the motor must be out of hot or contaminated air
Density at the fanAt about 120°C the gas density is close to 0.90 kg/m³, 75% of standard air. Pressure developed and power drawn fall in the same ratio, so the selection is made at this density and the motor is checked at cold start.

Supply, return and exhaust fans for heating, ventilation and air conditioning of plant and office space. Low pressure, so efficiency and noise govern. Client-stated blade types for the HVAC in general: Axial, backward inclined and forward curved.

Industries

Other fans in dyeing and finishing houses

HVAC in other processes

Services on this fan

Information needed to select or quote

  1. Duty point. Volume flow and static pressure at the fan inlet, with the gas density and temperature or the conditions to derive it.
  2. Operating conditions. Site altitude, normal operating temperature and continuous or intermittent duty.
  3. Gas stream. Dust loading and particle size, corrosive species, moisture, upset temperature and any tendency of the material to deposit on the impeller.
  4. Mechanical. Rotation viewed from the drive end, discharge orientation and motor power.

Send us your duty point

Flow, pressure, gas condition and temperature are enough to start a selection.

Get a quote